Technical data
12.5 Electromagnetic compatibility of the converters
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
227
Basic standard
for test proce-
dures
High-frequency electromagnetic field, ampli-
EN 61000-4-3 80 MHz – 1000 MHz, 10 V/m,
A
See the two tables below.
1) Reduction of motor speed
2) Shutdown on fault F00003 "Undervoltage"
3) Shutdown on fault F00002 "Overvoltage"
The requirements of the product standard for a drive system, according to C3, are fulfilled.
Operation with unshielded cable is not permitted.
Table 12- 8 Ground leakage currents to EN 61800-5-1 with 15 m CY shielded cable
Ground leakage currents (mA) at pulse frequency
ET 200pro FC-2 frequency converters in general industrial applications
Explanatory notes for general industrial application
In this EMC application, the manufacturer/assembler must certify the devices used as
compliant with the EMC directive for industrial environments. The limit values are in line with
the generic standards EN 61000-6-4 for generic emissions (noise radiation) and EN 61000-
6-2 interference immunity in the second environment (industrial).
Limit values for general industrial application
The following tables contain the key limit values for compliance with the generic standards.
Table 12- 9 Limit values for noise radiation for general industrial application to EN 61000-6-4
Basic standard for
test procedures