Installation
4.10 Mounting ET 200pro FC-2 fail-safe devices
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
49
Power transmission jumper
The power jumper connector is used to loop-through the main power from one frequency
converter/motor starter to the next converter/motor starter.
The table below shows the assignment of the contacts:
Table 4- 5 Power jumper connector
Pin
Socket
Assignment
1
1
Phase L1
2 2 Phase L2
3
3
Phase L3
4
4
Not assigned
PE
4.10
Mounting ET 200pro FC-2 fail-safe devices
In principle, fail-safe applications are configured the same as standard applications;
differences include:
A module must be inserted to the left of the frequency converter, via which the frequency
converter safety functions are controlled, e.g.
a repair switch module F-RSM
a F-Switch.
Only the following modules may be inserted between F-RSM or F-Switch and the
frequency converter:
400V switch off module
all direct or reversing starters
Procedure:
Mount them one after the other:
1. Module rack
2. Interface module
3. Bus module for F-RSM or F-Switch
4. Bus module for frequency converters
5. Termination module
6. Connection module for the interface module