Configure the fieldbus
7.2 PROFIenergy profile for PROFINET
SIMATIC ET 200pro FC-2 converter
94 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Error
value 1
Meaning
82 hex
Accepting the master control is inhibited via BI: p0806.
83 hex
Desired interconnection is not possible
(the connector output does not supply a float value although the con-
nector input requires a float value)
84 hex
Inverter does not accept a change request
(inverter is busy with internal calculations. See parameter r3996 in
the inverter List Manual. See also Section: Auto hotspot)
85 hex
No access methods defined.
86 hex
Write access only during commissioning of the data records (p0010 = 15)
(operating status of the inverter pre-
vents a parameter change.)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit
(change request to a value that lies within the "absolute" limits,
but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for the inverter power)
CC hex
Change request not permitted (change is not permitted as the access code is not available)
7.2
PROFIenergy profile for PROFINET
PROFIenergy is an energy management standard for production plants, based on the
PROFINET communication protocol. The functionality is certified and described in the
PROFIenergy profile of the PNO.
The control transfers the PROFIenergy commands in acyclic operation to the inverter in data
set 80A0 hex.
The inverters support the PROFIenergy profile V1.1 and the function unit class 3.
Parameters r5600 to p5614 are reserved for PROFIenergy functions in the inverter.
You can find further information about saving energy with PROFIenergy in the application
examplePROFIenergy -saving energy with SIMATIC S7
7.2.1
General inverter behavior when in the PROFIenergy energy-saving mode
When the PROFIenergy energy-saving mode is active, the inverter issues alarm A08800.
When the PROFIenergy energy-saving mode is active, the inverter does not send any
diagnostic alarms.
If the bus connection to the control system is interrupted while the inverter is in the
energy-saving mode, the inverter exits the energy-saving mode and resumes normal
operation.
The inverter changes into normal operation if the control system goes into the stop
condition while the inverter is in the energy-saving mode.
PROFIenergy energy-saving mode 2
Parameter r5600 shows the active PROFIenergy energy-saving mode.