Setting functions
8.9 Switchover between different settings
SIMATIC ET 200pro FC-2 converter
166 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
The reports and the machine documentation can also be found in the section: Acceptance
tests for the safety functions (Page 243).
Switchover between different settings
There are applications that require different inverter settings.
You connect different motors to one inverter. Depending on the particular motor, the inverter
must operate with the associated motor data and the appropriate ramp-function generator.
Your can set several inverter functions differently and then switch over between the different
settings.
The associated parameters are indexed (index 0, 1, 2 or 3). Using control commands select
one of the four indexes and therefore one of the four saved settings.
The settings in the inverter with the same index are called the drive data set.
Figure 8-27 Switching over between different settings using drive data sets (DDS)