Setting functions
8.7 Application-specific functions
SIMATIC ET 200pro FC-2 converter
140 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
If the load of the motor is so large during stationary operation that the motor current reaches
the current limit, the I-max controller reduces the speed and the motor voltage until the motor
current is in the permissible range again.
If the motor current reaches the current limit during deceleration, the I-max controller extends
the deceleration operation.
Settings
You only have to change the factory settings of the I-max controller if the drive tends to
oscillate when it reaches the current limit or if it is shut down due to overcurrent.
Table 8- 14 I-max controller parameters
Parameter
Description
p0305
Rated motor current
p0640
Motor current limit
p1340
Proportional gain of the I-max controller for speed reduction
p1341
Integral time of the I-max controller for speed reduction
r0056.13
Status: I-max controller active
r1343
Speed output of the I-max controller
Shows the amount to which the I-max controller reduces the speed.
For more information about this function, see function diagram 6300 in the List Manual.
8.7
Application-specific functions
8.7.1
Functions that match the application
The converter offers a series of functions that you can use depending on your particular
application:
Unit changeover (Page 141)
Braking functions
Braking the motor electrically (Page 145)
Motor holding brake (Page 148)
Automatic restart
Details can be found in the List Manual from parameter p1210, see also: Manuals for
your inverter (Page 248).