Setting functions
8.4 Setpoint calculation
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
107
Additional information about binary selection can be found in function diagram 3010 in the
List Manual.
Parameter for setting the fixed setpoints
Parameter
Description
p1001
Fixed speed setpoint 1 (factory setting: 0 rpm)
p1002
Fixed speed setpoint 2
(factory setting: 0 rpm)
...
...
p1015
Fixed speed setpoint 15
(factory setting: 0 rpm)
p1016
Fixed speed setpoint mode (factory setting: 1)
1:
Direct
2:
Binary
p1020
Fixed speed setpoint selection bit 0 (factory setting: 0)
p1021
Fixed speed setpoint selection bit 1 (factory setting: 0)
p1022
Fixed speed setpoint selection bit 2 (factory setting: 0)
p1023
Fixed speed setpoint selection bit 3 (factory setting: 0)
r1024
Fixed speed setpoint effective
r1025.0
Fixed speed setpoint status
1 signal
Fixed speed setpoint is selected
8.4
Setpoint calculation
8.4.1
Overview of setpoint processing
The setpoint can be modified as follows using the setpoint processing:
Invert setpoint to reverse the motor direction of rotation (reversing).
Inhibit positive or negative direction of rotation, e.g. for conveyor belts, pumps or fans.
Skip frequency bands to prevent mechanical resonance effects.
The skip frequency band at speed = 0 results in a minimum speed after switching on the
motor.
Limit to a maximum speed to protect the motor and mechanical system.
Ramp-function generator to accelerate and brake the motor with an optimum torque.
Figure 8-9 Setpoint processing in the converter