EasyManua.ls Logo

Siemens SIMATIC ET 200pro - STEP 7 Program Examples; Data Exchange Via the Fieldbus

Siemens SIMATIC ET 200pro
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.2 STEP 7 program examples
SIMATIC ET 200pro FC-2 converter
230 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
A.2
STEP 7 program examples
A.2.1
Data exchange via the fieldbus
Data exchange via the fieldbus
Analog signals
The inverter always scales signals that are transferred via the fieldbus to a value of 4000
hex.
Table A- 1 Signal category and the associated scaling parameters
Signal category
4000 hex ≙ …
Speeds, frequencies
p2000
Voltage p2001
Current
p2002
Torque p2003
Power
r2004
Temperature
p2006
Control and status words
Control and status words consist of a high byte and a low byte. A SIMATIC control interprets
words differently than the inverter: The higher and lower-order bytes are interchanged when
they are transferred. See also the following program example.