Technical data
12.4 Pulse frequency and current reduction
SIMATIC ET 200pro FC-2 converter
222 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
12.4
Pulse frequency and current reduction
Relationship between pulse frequency, temperature and output base-load current
Figure 12-1 Power derating in relation to the ambient temperature and pulse frequency
Table 12- 2 Current reduction depending on pulse frequency
Rated power
based on HO
Rated output current at pulse frequency of
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
1.5 kW @45 °C
3.9
3.9
3.9
3.6
3.3
2.7
2.2
1.1 kW @55 °C
3.5
2.8
2.2
1.6
1.1
0.5
0.0
12.5
Electromagnetic compatibility of the converters
12.5.1
Electromagnetic compatibility
Electromagnetic compatibility (EMC)
All manufacturers/assemblers of electrical units which "perform an essentially complete
function and are marketed as a single unit designed for the end-user", must comply with the
EMC Directive 89/336/EEC.
There are three ways for the manufacturer/assembler to verify compliance:
Self-certification
The manufacturer declares that the European standards applicable to the electrical
environment for which the unit is intended are satisfied. Only standards which have been
officially published in the official journal of the European Union are allowed to be cited in the
manufacturer's declaration.