Setting functions
8.9 Switchover between different settings
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
167
You can use parameter p0180 to define the number of drive data sets (1 or 2).
Table 8- 23 Selecting the number of
Drive commissioning: Data sets
p0180
Drive data sets (DDS) number
(factory setting: 1)
Drive commissioning: Ready
Table 8- 24 Parameters for switching the drive data sets:
p0820
Drive data set selection DDS
Motor changeover, motor number
Displaying the number of the DDS that is currently effective
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the Parameter Manual.
Note
You can only switch over the motor data of the drive data sets in
the "ready for operation"
state with the motor switched
-off. The switchover time is approx. 50 ms.
If you do not switch over the motor data together with the drive data sets (i.e. same motor
number in p0826), then the drive data sets can also be switched o
ver in operation.
Table 8- 25 Parameters for copying the drive data sets
For more information, see the List Manual (the parameter list and function diagram 8565).