Configure the fieldbus
7.1 PROFIdrive profile for PROFIBUS and PROFINET
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
93
Table 7- 7 Error value in the parameter response
Illegal parameter number (access to a parameter that does not exist)
01 hex
Parameter value cannot be changed
(change request for a parameter value that cannot be changed)
Lower or upper value limit exceeded (change request with a value outside the value limits)
Incorrect subindex (access to a parameter index that does not exist)
No array (access with a subindex to non-indexed parameters)
Incorrect data type (change request with a value that does not match the data type of the parameter)
Setting not permitted, only resetting (change request with a value not equal to 0 without permission)
Descriptive element cannot be changed (change request to a descriptive element that cannot be changed)
Description data not available (access to a description that does not exist, parameter value is available)
No master control (change request but with no master control)
0F hex
Text array does not exist
(although the parameter value is available, the request is made to a text array that
11 hex
Request cannot be executed due to the operating state
(access is not possible for temporary reasons that are
14 hex
(change request with a value that is within the limits but which is illegal for other permanent
reasons, i.e. a parameter with defined individual values)
Response too long (the length of the actual response exceeds the maximum transfer length)
16 hex
Illegal parameter address
(illegal or unsupported value for attribute, number of elements, parameter number,
subindex or a combination of these)
Illegal format (change request for an illegal or unsupported format)
18 hex
Number of values not consistent
(number of values of the parameter data to not match the number of elements
in the parameter address)
Drive object does not exist (access to a drive object that does not exist)
Parameter text cannot be changed
Service is not supported (illegal or not support request ID).
6B hex
The change request is not possible when the controller is enabled
. (The inverter rejects the change request as
the motor is switched on. Please observe the "Can be changed" parameter attribute (C1, C2, U, T) in the List
Manual. See also Section: Auto hotspot)
Change request is only possible when the motor is being commissioned (p0010 = 3).
Change request is only possible when the power unit is being commissioned (p0010 = 2).
Change request is only possible for quick commissioning (basic commissioning) (p0010 = 1).
Change request is only possible if the inverter is ready (p0010 = 0).
Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30).
Change request possible only during commissioning of the safety functions (p0010 = 95).
Change request is only possible when a technological application/unit is being commissioned (p0010 = 5).
Change request is only possible in a commissioning state (p0010 ≠0).
Change request is not possible for internal reasons (p0010 = 29).
Change request is not possible during download.
Change request is not possible during download.