Configure the fieldbus
7.1 PROFIdrive profile for PROFIBUS and PROFINET
SIMATIC ET 200pro FC-2 converter
92 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Data block
Byte n
Bytes n + 1
n
Values, parameter 1
Format
02 hex:
Integer 8
03 hex:
Integer 16
04 hex:
Integer 32
05 hex:
Unsigned 8
06 hex:
Unsigned 16
07 hex:
Unsigned 32
08 hex:
Floating Point
10 hex
Octet String
13 hex
Time Difference
41 hex:
Byte
42 hex:
Word
43 hex:
Double word
Number of index values
00 hex ... EA hex
Value of the 1st Index
…
Values, parameter 2
…
…
…
Values, parameter m
…
Table 7- 5 Response, if the inverter has executed the change request
Data block
Byte n
Bytes n + 1
n
Header
Reference (identical to a change request)
02 hex (change request successful)
0
01 hex
(ID of drive objects, at G120
al-
ways = 1)
Number of parameters
(identical to a change
request)
2
Table 7- 6 Response if the inverter was not able to completely execute the change request
Data block
Byte n
Bytes n + 1
n
Header
Reference
(identical to a change request)
82 hex:
(Inverter was not able to completely
execute the write request)
0
01 hex
(ID of drive objects, at G120
al-
ways = 1)
Number of parameters
(identical to a change
request)
2
Values, parameter 1
Format
40 hex: Zero (change request for this data
block executed)
44 hex: Error (change request for this data
block not executed)
Number of error values
00 hex
01 hex or 02 hex
4
Only for "Error" -
error value 1
You can find the error values in the table at the end of this section.
6
Only for "Error" -
error value 2
Error value 2 is either zero, or it contains the number of the first index where the error oc-
curred.
8
Values, parameter 2
...
...
…
…
Values, parameter m
...