Setting functions
8.6 Protection and monitoring functions
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
137
Using a KTY sensor, the converter monitors the motor temperature and the sensor
itself for wire
-break or short-circuit:
● Temperature monitoring:
The converter uses a KTY sensor to evaluate the motor temperature in the range from -
48° C ... +248° C.
Use the p0604 or p0605 parameter to set the temperature for the alarm and fault
threshold.
– Overtemperature alarm (A07910):
- motor temperature > p0604 and p0610 = 0
– Overtemperature fault (F07011):
The converter switches off with fault in the following cases:
- motor temperature > p0605
- motor temperature > p0604 and p0610 ≠ 0
● Sensor monitoring (A07015 or F07016):
– Wire-break:
The converter interprets a resistance > 2120 Ω as a wire-break and outputs the alarm
A07015. After 100 milliseconds, the converter changes to the fault state with F07016.
– Short-circuit:
The converter interprets a resistance < 50 Ω as a short-circuit and outputs the alarm
A07015. After 100 milliseconds, the converter changes to the fault state with F07016.
Setting parameters for the temperature monitoring
p0335
Specify the motor cooling
0: Natural cooling - with fan on the motor shaft (factory setting)
1: Forced ventilation - with a separately driven fan
2: Liquid cooling
128: No fan
p0601
Motor-temperature sensor type
0: No sensor (factory setting)
1: PTC (→ p0604)
2: KTY84 (→ p0604, p0605)
Motor temperature alarm threshold (factory setting 130° C)
p0605
Motor temperature fault threshold
(factory setting 145° C)
Setting for KTY84 sensor. The parameter has no significance for a PTC sensor.