Setting functions
8.8 Safe Torque Off (STO) safety function
SIMATIC ET 200pro FC-2 converter
164 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
After a component has been replaced or the firmware updated, a reduced acceptance test of
the safety functions must be performed.
Replacing the inverter with an
identical type
No.
Only check the direction of
rotation of the motor.
• Supplement inverter data
• Log the new checksums
• Countersignature
• Supplement the hardware
version in the inverter data.
Replace the motor with an identi-
No change.
Replace the gearbox with an iden-
Replace the safety-related periph-
erals (e.g. Emergency Off switch).
No.
Only check the control of the
safety functions affected by
the components that have
No change.
Inverter firmware update. No.
• Supplement firmware version
in the inverter data
• Log the new checksums
• Countersignature.
The STARTER provides you with a number of documents to be regarded as a
recommendation for the acceptance tests of the safety functions.