Commissioning
6.5 Basic commissioning
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
81
Select the application for the inverter:
Low overload for applications that only require a low dynamic pe
rfor-
mance, e.g. pumps or fans.
High overload for applications requiring a high dynamic perfo
rmance, e.g.
cording to the rating plate of your motor.
If you have selected a motor based on its article number, the data has
already been entered.
If you have set the "Speed control" control mode, then we reco
mmend
setting "[1] Identify motor data at standstill and with motor rotating".
With this setting,
the inverter opt
i-
mizes its speed
controller.
If one of the following cases is applicable, select the setting "[2]
Identify
motor data at standstill":
You have selected "Speed control" as control mode, however the
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
You have set "V/f control" as control mode.
Set the most important parameters to suit your application.
g "Calcu-
Set the check mark for "RAM to
ROM (save data in the drive)" to
save your data in the inver
ter so
that it is not lost when the power
fails.
Exit basic commissioning.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.