5-31
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Result: COM ET 200 asks for a station number.
3. In the STATION NUMBER input field, enter the number of the faulty
station that you want to investigate further.
4. Press <F6> (ENTER) to be able to evaluate the diagnostics messages of
this station.
Result: COM ET 200 goes to another screen. The screen that appears next
depends on the type of station you are investigating.
ENTER
Station diagnostics:
0123456789101112131415
KH = 10
Identifier–related diagnostics:
Slot:
0149
Aktiv
HELP EXIT
F2 F3 F4 F8F1
Station number: 3
Program file selected: B:TEST@@ET.200
SIMATIC S5 / COM ET 200
INDIVIDUAL DIAGNOSTICS
Station type: ET 200U–DP
Station name: PRESS
Station status: Station cannot be forced by PLC
HELP EXIT
F2 F3 F4 F8F1
SLOT
Figure 5-11 INDIVIDUAL DIAGNOSTICS Screen
Up to 4 diagnostic messages can be displayed in the STATION STATUS
field.
STATION DIAGNOSTICS uses the “KH” format. See Figure 5–15 for details
on the structure of the station diagnostics.
In the IDENTIFIER–RELATED DIAGNOSTICS field the slots are indicated
from which the diagnostics signals originate.
ET 200U(DP Standard): AddressAssignm.,Starting–Up, DiagnosingFaultsUsing COM ET 200