4-10
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 4-1 Address IDs for the Modules in an ET 200U(DP Siemens) Station
Order Num-
ber of Module
Address ID
ET 200U
(DP Siemens)
Address
Scope
(Byte)
Delay
Time
(ms)
1
Address
Area
Current
Consump-
tion (mA)
Power
Loss
(W)
Digital Inputs 6ES5 ...:
420–8MA11 4DI or 008 1 2.5 to 5 Digital 16 0.8
421–8MA12 8DI or 009 1 2.3 to 4.5 Digital 34 1.6
422–8MA11 027 2* 3 to 4 Digital or
analog
50 4.5
430–8MB11 4DI or 008 1 1.4 to 5 Digital 5 2
430–8MC11 4DI or 008 1 10 to 20 Digital 16 2.8
430–8MD11 4DI or 008 1 10 to 20 Digital 16 2.5
431–8MA11 8DI or 009 1 4 to 5.5 Digital 32 2
431–8MC11 8DI or 009 1 10 to 20 Digital 32 2.5
431–8MD11 8DI or 009 1 10 to 20 Digital 32 3.6
433–8MA11 8DI or 009 1 1 to 10 Digital 6 2.4
437–8EA12 4DI or 008 1 40 Digital 50 0.45
Digital Outputs 6ES5 ...:
440–8MA11 048 1 < 1 Digital 15 3
440–8MA21 048 1 < 1 Digital 15 4.8
441–8MA11 8DQ or 017 1 < 1 Digital 14 3.5
450–8MB11 048 1 < 1 Digital 15 5
450–8MD11 4DQ or 016 1 < 1 Digital 14 3.5
451–8MA11 8DQ or 017 1 < 1 Digital 24 4
451–8MD11 8DQ or 017 1 < 1 Digital 25 3.5
451–8MR11 8DQ or 017 1 < 1 Digital 30 1.6
451–8MR12 8DQ or 017 1 < 1 Digital 30 1.6
452–8MR11 4DQ or 016 1 < 1 Digital 14 2
453–8MA11 8DQ or 017 1 < 1 Digital 20 1
457–8EA12 048 1 < 1 Digital 55 0.5
* The address scope is necessary for the inputs and the outputs (i.e. if the address scope is 2 bytes, 2 bytes are used
for the inputs and 2 bytes are used for the outputs). Since COM ET 200 assigns the addresses for these modules
optionally, inputs and outputs can have different start addresses.
1 For an input module, the delay time is the time between a signal change at an input and a change of state on the I/O
bus. For an output module, the delay time is the time between a signal change on the I/O bus and a change of state
at an output.
ET 200U(DP Siemens): AddressAssignment,Starting–Up,Diagnosing Faults Using COMET200