6-8
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
6.2 Settings of the IM 318–C
There are two possibilities for setting the IM 318–C which also depend on
the mode selected:
1. Set a valid station number on the bank of switches on the IM 318–C
(³ Table 6-5).
2. Set switch 8 on the bank to “DP Standard”.
If the ready period of the FMS master cannot be set within the range
T
RDY
t min_T
SDR
= 11T
Bit
, select “FMS Standard”. This, however,
extends the response times (³ Table 6-3).
Table 6-5 Setting the Station Number and Switch 8
Settings ET 200U
(FMS)
ET 200U in a
Mixed Config.
Combi–Slave
Valid station number: 1 to 125 3 to 124 3 to 124
Setting of switch 8: DP Standard DP Standard DP Standard
Setting the Station
Number and
Switch 8
ET 200U(DP Standard/FMS): Modes, Settings and Comm. Capabilities of IM 318–C