EasyManua.ls Logo

Siemens SIMATIC S5 ET 200U - Diagnostics Data Object

Siemens SIMATIC S5 ET 200U
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-19
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
The “diagnostics data” object contains the diagnostics messages of the
ET 200U(DP Standard/FMS). The FMS master can read the “diagnostics
data” object.
The following tables show the structure of the “diagnostics data” object and
the diagnostics messages, respectively.
Table 6-13 “Diagnostics Data” Object
INDEX: 110
OBJECT_CODE: 7 (Simple–Variable)
DATA_TYPE_INDEX: 10 (Octet string)
LENGTH: 13
LOCAL ADDRESS:
PASSWORD:
ACCESS_GROUPS:
ACCESS_RIGHTS: R
NAME[16]: Diagnostics data
EXTENSION_LENGTH: 0
The length of the diagnostics messages is 13 octets:
Table 6-14 Structure of the Diagnostics Messages of the ET 200U(DP Standard/
FMS)
Octet Diagnostics Message
1 Station status 1
2 Station status 2
3 Station status 3
4 DP master address
5 Manufacturer identification (I)
6 Manufacturer identification (II)
7 Header (station diagnostics)
8 Station diagnostics
9 Header (module diagnostics)
10 Module diagnostics (slots 0 to 7)
11 Module diagnostics (slots 8 to 15)
12 Module diagnostics (slots 16 to 23)
13 Module diagnostics (slots 24 to 31)
The following tables describe the meanings of the various diagnostics mes-
sages: