4-12
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 4-3 Address IDs for the Modules in an ET 200U(DP Siemens)
Order Num-
ber of Module
Address ID
ET 200U
(DP Siemens)
Address
Scope
(Byte)
Delay
Time
(ms)
1
Address
Area
Current
Consump-
tion (mA)
Power
Loss
(W)
Input/Ouput Module:
482–8MA11
–8MA12
–8MA13
027 2* Digital
or
analog
50 4.5
Power Supply Module:
935–8ME11
1
4DI/4DI or
008/008
– Digital 7.5
Simulator Module:
788–8MA11
8DI or 009
< 0.2
Digital
0.3
8DQ or 017
1 30
Timer Module:
380–8MA11 4DX or 024 1* Digital 10
Counter Modules:
385–8MA11 4DX or 024 1* 0.18 Digital 20 2.5
385–8MB11 2AX or 029 4* Analog 70 1.9
Comparator Module:
461–8MA11 4DI or 008 1 5 Digital 35 0.3
PID Controller Modules:
2
262–8MA11
–8MA12
223 8* 100 to 200 Analog 20
262–8MB11
–8MB12
223 8* 100 to 200 Analog 20
Position Control Modules:
263–8MA11
1
223/000 8* Analog 120 4
266–8MA11 223 8* Analog
267–8MA11 093 4* Analog 150
* The address scope is necessary for the inputs and the outputs (i.e. if the address scope is 2 bytes, 2 bytes are used
for the inputs and 2 bytes are used for the outputs). Since COM ET200 assigns the addresses for these modules
optionally, inputs and outputs can have different start addresses.
1 The module occupies 2 slots.
2 You can address a PID controller module in an ET 200 system at least every 200 ms. You cannot use function
blocks FB61 and FB62.
ET 200U(DP Siemens): AddressAssignment,Starting–Up,Diagnosing Faults Using COMET200