7-19
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 7-8 Analog Input Module 464–8MF11, 2 PT 100 (Unipolar)
Analog Input Module 464–8MF21, 2 PT 100 “No Linearization” (Unipolar)
Units Resistance in High Byte Low Byte Range
>4095 w400.0 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 Overflow
4095
2049
399.90
200.098
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
0
0
0
0
0
0
Overrange
2048 200.0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1024 100.0 0 010000000000000
1 0.098 0 000000000001000
om
na
ange
0 0.0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Table 7-9 Analog Input Module 464–8MF21, 2 PT 100 “with Linearization” (Bipolar), to DIN IEC 751
Units Resistance
in
Tempera-
ture in °C
High Byte Low Byte Range
>1766 >400 >883 0 0 1 1 0 1 1 1 0 0 1 1 0 0 0 1 Overflow
1766
1702
883
851
0
0
0
0
1
1
1
1
0
0
1
1
1
0
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
1
1
Overrange*
1700 390.26 850 0 0 1 1 0 1 0 1 0 0 1 0 0 0 0 0
1400 345.13 700 0 010101111000000
1000 280.90 500 0 001111101000000
600 212.02 300 0 001001011000000
300 157.31 150 0 000100101100000
200 138.50 100 0 000011001 0 0 0 0 0 0 Nominal Range
2 100.39 1 0 000000000010000
0 100.00 0 0 000000000000000
–40 92.16 –20 1 111111011000000
–80 84.27 –40 1 111110110000000
–200 60.25 –100 1 111100111000000
–202
–494
–101
–247
1
1
1
1
1
1
1
1
1
0
0
0
0
0
1
0
1
1
0
0
1
0
1
1
0
0
0
0
0
0
1
1
Overrange*
<–494 <–247 1 1 1 1 0 0 0 0 1 0 0 1 0 0 0 1 Overflow
* In the overrange, the current slope of the characteristic curve is maintained when leaving the linearized nominal range.
Analog Value Processing