4-11
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 4-2 Address IDs for the Modules in an ET 200U(DP Siemens)
Order Num-
ber of Module
Address ID
ET 200U
(DP Siemens)
Address
Scope
(Byte)
Delay
Time
(ms)
1
Address
Area
Current
Consump-
tion (mA)
Power
Loss
(W)
Analog Inputs 6ES5 ...:
464–8MA11
1
1–channel: 1–ch.: 1–channel: Analog 70 0.7
464–8MA21
1
1AI or 012, 2 60 100 0.7
464–8MB11
1
2–channel: 2–ch.: 2–channel: 70 0.7
464–8MC11
1
2AI or 013, 4 120 70 0.7
464–8MD11
1
4–channel: 4–ch.: 4–channel: 70 0.7
464–8ME11
1
4AI or 015 8 240 70 0.7 to 1
464–8MF11
2
1–channel: 1–ch: 1–channel: Analog 70 0.9
1AI or 012, 2 60
464–8MF21
2
2–channel: 2–ch.: 2–channel: Analog 100 0.9
2AI or 013 4 120
466–8MC11 2AI or 013 4 20 Analog 100 0.9
467–8EE11
2
1–channel:
1AI or 012,
1–ch.:
2
1–channel: Analog 320 0.7 to 3
2–channel: 2–ch.: 2–channel:
2AI or 013 4
Analog Outputs 6ES5 ...:
470–8MA11 2AQ or 021 4 0.1 Analog 3.1
470–8MA12 2AQ or 021 4 0.15 Analog 3.1
470–8MB11 2AQ or 021 4 0.1 Analog 3.8
470–8MB12 2AQ or 021 4 0.15 Analog 3.8
470–8MC11 2AQ or 021 4 0.1 Analog 3.8
470–8MC12 2AQ or 021 4 0.15 Analog 3.8
470–8MD11 2AQ or 021 4 0.1 Analog 3.1
470–8MD12 2AQ or 021 4 0.15 Analog 3.1
470–8MD21 2AQ or 021 4 Analog
477–8EC11 2AX or 029 4* Analog 350 3.2
* The address scope is necessary for the inputs and the outputs (i.e. if the address scope is 2 bytes, 2 bytes are used
for the inputs and 2 bytes are used for the outputs). Since COM ET 200 assigns the addresses for these modules
optionally, inputs and outputs can have different start addresses.
1 With these analog modules, you can use one, two, or four channels.
2 With these analog modules, you can use one or two channels.
ET 200U(DP Siemens): AddressAssignment,Starting–Up,Diagnosing Faults Using COMET200