6-27
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
The “DP inputs” object can be used by the FMS master to read all inputs of
an ET 200U(DP Standard/FMS) assigned to a DP master.
Table 6-26 “DP Inputs” Object
INDEX: 130
OBJECT_CODE: 7 (Simple–Variable)
DATA_TYPE_INDEX: 10 (Octet–String)
LENGTH: Depending on configuration of
ET 200U(DP Standard/FMS)
LOCAL ADDRESS:
PASSWORD:
ACCESS_GROUPS:
ACCESS_RIGHTS: R
NAME[16]: DP Input
EXTENSION_LENGTH: 0
The “FMS inputs” object can be used by the FMS master to read all inputs of
an ET 200U(DP Standard/FMS) assigned to an FMS master.
The “FMS inputs” object has the following structure:
Table 6-27 “FMS Inputs” Object
INDEX: 140
OBJECT_CODE: 7 (Simple–Variable)
DATA_TYPE_INDEX: 10 (Octet–String)
LENGTH: Depending on configuration of
ET 200U(DP Standard/FMS)
LOCAL ADDRESS:
PASSWORD:
ACCESS_GROUPS:
ACCESS_RIGHTS: R
NAME[16]: FMS Input
EXTENSION_LENGTH: 0