6-30
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
6.3.3 List of Communication Links (KBL)
The list of communication links (KBL) contains all the associations between
the ET 200U(DP Standard/FMS) and the FMS master. The communication
links are relevant for configuring the FMS master.
The list of communication links is based on the definitions in the sensors/ac-
tuators profile.
The list of communication links is followed by the definitions of the terms
employed.
Table 6-31 Master–Slave, Cyclic, Read
KR Type ATTR Local
LSAP
RSAP RADR SCC RCC SAC RAC ACI,
CCI
2 MSZY O 20 All All 0 0 0 0 3000
Max. PDU Size
Features Supported FMS Services Supported
Send
HiPrio
Send
LoPrio
Rec.
HiPrio
Rec.
LoPrio
0 241 0 241 00 00 00 00 20 00 Read.ind
Table 6-32 Master–Slave, Cyclic, Write
KR Type ATTR Local
LSAP
RSAP RADR SCC RCC SAC RAC ACI,
CCI
3 MSZY O 21 All All 0 0 0 0 3000
Max. PDU Size
Features Supported FMS Services Supported
Send
HiPrio
Send
LoPrio
Rec.
HiPrio
Rec.
LoPrio
0 241 0 241 00 00 00 00 10 00 Write.ind
Table 6-33 Master–Slave, Cyclic, with Slave Initiation, Read
KR Type ATTR Local
LSAP
RSAP RADR SCC RCC SAC RAC ACI,
CCI
4 MSZY_SI O 22 All All 0 0 1 0 3000
Max. PDU Size
Features Supported FMS Services Supported
Send
HiPrio
Send
LoPrio
Rec.
HiPrio
Rec.
LoPrio
241 241 0 241 00 00 10 00 20 00 Read.ind