4.3.1 Using LEDs to Diagnose Problems
Figure 4-8 Fault LEDs on the ET 200U Interface Module
Table 4-7 LED Fault Messages on ET 200U Interface Module
LED Optical
Signal
Explanation
RUN Lit Normal operation (load voltage supply
available)
BUS–FAULT Lit
Response time has run out and the
IM 318–B interface module was not ad-
dressed.
During system start–up or power up:
IM 318–B not parameterized yet.
No connection between SINEC L2–DP
bus and slave station.
IM–FAULT Lit or
flashing
There is a fault in the I/O bus (e.g. a bus
unit is defective).
BUS–FAULT
and
IM–FAULT
Lit
There is a hardware fault in the ET 200U
interface module.
BUS–FAULT
and
IM–FAULT
Flashing
The configured station address is not within
the permitted range (3 to 124).
ET 200U(DP Siemens): AddressAssignment,Starting–Up,Diagnosing Faults Using COMET200