EasyManua.ls Logo

Siemens SIMATIC S5 ET 200U - Structure of Station Diagnostics and Module Diagnostics

Siemens SIMATIC S5 ET 200U
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-33
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
The station status, the station diagnostics and the identifier–related diagnos-
tics (module diagnostics) are described in this manual as they are typical for
the ET 200U slave station.
The diagnostics function is loaded and transferred:
L KY (Station number),(code) Station number: 3 to 124
Code: 0, ..., 7
T PW 252 Afterwards the station diagnos-
tics is transferred into the “diag-
nostics address” byte (here I/O
byte 252)
16 bytes per slave station are reserved for station status, station diagnostics
and module diagnostics. The 16 bytes are organized in 8 words. They are
structured as follows:
Table 5-12 Structure of Station Diagnostics and Module Diagnostics
Code Diagnostics Address Diagnostics Address + 1
0 Station status 1 Station status 2
1 Station status 3 Master address
2 Manufacturer identification
3 Header Station diagnostics
4 Header Identifier–related diagnostics
(module diagnostics)
(slots 0 to 7)
5 Identifier–related diagnostics
(module diagnostics)
(slots 8 to 15)
Identifier–related diagnostics
(module diagnostics)
(slots 16 to 23)
6 Identifier–related diagnostics
(module diagnostics)
(slots 24 to 31)
Unassigned
7 Unassigned Unassigned
Note
If a module signals diagnostics, a delay of up to 150 ms is possible between
input into the station diagnostics and the following input into the identifier–
related diagnostics.
Structure and Re-
quest of Station
Diagnostics for
ET 200U
ET 200U(DP Standard): AddressAssignm.,Starting–Up, DiagnosingFaultsUsing COM ET 200

Table of Contents

Related product manuals