7-15
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Set the switches on analog module 464–8MF21 as illustrated in Table 7-3.
Table 7-3 Settings for the Operating Mode Switch for Analog Input Module
464–8MF21
Function Settings for Operating Mode Switch
Power Supply Fre-
quency
50 Hz
8
7
6
5
4
3
2
1
60 Hz
8
7
6
5
4
3
2
1
Operation
1 Channel (Ch 0)
8
7
6
5
4
3
2
1
2 Channels (Ch 0 to
Ch 1)
8
7
6
5
4
3
2
1
Wire Break
With
Wire Break Signal
8
7
6
5
4
3
2
1
No
Wire Break Signal
8
7
6
5
4
3
2
1
Characteristic Lineari-
zation for the PT 100
No Linearization
8
7
6
5
4
3
2
1
Linearization
for PT 100
8
7
6
5
4
3
2
1
Positions 1 and 2 on the operating mode switch have no function.
If you set the switch to “no linearization” and “no temperature compensa-
tion,” module 464–8MF21 functions just like module 464–8MF11.
Characteristic linearization is possible for the following temperature ranges:
PT 100: – 100 _C ... + 850 _C (in steps of 0,5 _C).