EasyManua.ls Logo

Siemens SIMATIC S5 ET 200U - Page 99

Siemens SIMATIC S5 ET 200U
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-32
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
76543210 76543210
Diagnostics Word “Station status 1 and station status 2”, code = 0
Diagnostics address
“Station status 1”
Diagnostics address + 1
“Station status 2”
1: Slave station has not been configured with COM ET 200.
0: Bit is always “0”.
1: Slave station cannot be accessed.
1: Slave station is not yet ready for data exchange.
1: The configuration data sent from the master to the slave station do not corre–
spond with the structure of the slave station.
1: Station diagnostics or module diagnostics are in operation.
0: Bit is always “0”.
0: Bit is always “0”.
0: Bit is always “0”.
1: Response monitoring has been activated.
1: Bit is always “1”.
0: Bit is always “0”.
1: Slave station is not an ET 200U (parameter assignment error).
1: Slave station cannot continue operation if
the fault has not been remedied.
1: Slave must be reparameterized.
1: Slave station has been parameterized from another master.
Figure 4-11 Structure of the Diagnostics Word after Request of the Station Status (Station Status 1 and Station
Status 2)
76543210 76543210
Diagnostics Word “Station status 3 and master address”, code = 1
Irrelevant Address of master which has
parameterized the slave station
Diagnostics address
“Station status 3”
Diagnostics address + 1
“Master address”
Figure 4-12 Structure of the Diagnost. Word after Request of the Station Status (Station Status 3 and Master Address)
ET 200U(DP Siemens): AddressAssignment,Starting–Up,Diagnosing Faults Using COMET200

Table of Contents

Related product manuals