Logic Modules
13.8 Limit Monitor
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
125
Functional principle
The limit signal issued depends on:
● The operating state of the motor
● The TPF function
● The parameterized "activity".
Hysteresis for Limit Monitor
You can set the hysteresis for limit monitors here:
0 - 15 % of the threshold value in 1 % increments (5 %)
Note
When using Limit Monitors, always ensure that the correct range and unit are used for the
analog values connected to the limit input. These always have a direct
influence on the unit
of the limit value to be set.
Examples of typical units and ranges in SIMOCODE pro:
Temperatures (e.g. max. temperature)
- 4294967295
Currents (e.g. max. current I_max)
e
Thus, for example, a limit value of 473 (K) should be parameterized for a Limit Monitor to
monitor a maximum temperature of 200 °C.