Online Settings and Displays
17.12 Status Information
SIMOCODE PRO V PN FDI
164 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
17.12 Status Information
Status Information
Different events are indicated in the plain language in the "Events" register of the Target
system > Faults/Warnings/Status information mask:
Indication
Meaning/Possible cause/Acknowledgement/Error processing
Parameter blocking during startup
active
The start-up parameter block prevents SIMOCODE pro
parameters which could be saved in the controller from being
accepted.
The block must be set when SIMOCODE ES or Device
Integration Manager is used for parameterizing.
The block may not be set when SIMOCODE pro is integrated in
STEP 7 via the SIMOCODE pro Object Manager (OM) or
SIMOCODE pro C was parameterized via GSD.
Configuration fault The configured device configuration does not match the current
configuration.
Please check if all configured components are present.
Check the actual configuration using "Configuration".
Rectify the fault; Reset.
Required function is not supported At least one parameterized function is not supported by the
product version of the Basic Unit.
Only activate functions that are supported by the product
version of the Basic Unit. For example, SIMOCODE pro V
Basic Units with the product version E01 do not support the
voltage measuring module, the temperature module and the
analog module.
Parameter is faulty There is a fault in the parameter data transmitted to the device.
Faults can occur in the parameter data, for example, if the
device parameterization was not carried out with SIMOCODE
ES or Device Integration Manager.
Check the parameter data (data records 130 - 133)
transmitted to the device to make sure that the contents are
correct.
Changing of the parameters is not
permissible in the current mode
Changing of a least one parameter is not possible in the current
operating state. A lot of parameters can only be changed when
the motor feeder is switched off and is not in the "Remote"
operating mode.
Wrong password The SIMOCODE pro parameters are protected by a password.
An attempt was made to change the parameters without
entering the password.
If you do not know the password, new parameters cannot be
set until the factory default settings have been reset.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals