Monitoring Functions
9.2 Current Limits
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
49
9.2 Current Limits
9.2.1 Current Limits
Current Limits
Current limit monitoring is used for process monitoring, independent of overload.
SIMOCODE pro supports two-phase monitoring of the motor current for freely-selectable
upper and lower current limits.
The response of SIMOCODE pro when an pre-warning or trip level has been reached can be
freely parameterized and delayed.
Motor current measurement is carried out via current measuring modules or current/voltage
measuring modules.
Hysteresis
Here you can set the hysteresis for the current limits:
Range
0 to 15 % of the threshold value in 1% increments
Preset
5 %