Monitoring Functions
9.1 Earth Fault
SIMOCODE PRO V PN FDI
48 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Response at warning level
Here you can set how SIMOCODE pro should respond if the warning level is undershot.
Response
Warning level
Disabled
X
Signaling
X
Warning
X
Tripping
-
Delay
0 - 25.5 s
1)
Preset
0.1 s
1)
Additional delay of the residual current transformer delay
Hysteresis
Here you can set the hysteresis for the earth-fault current:
Hysteresis earth-fault current
0 - 15% of the level value in 1% increments
Preset
5 %
Response at sensor fault
Here you can set how SIMOCODE pro should respond to a sensor fault:
Response
Sensor fault
Disabled
X
Signaling
X
Warning
X
Tripping
-