Online Settings and Displays
17.10 Faults
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
153
17.10 Faults
Faults
Different warnings are indicated via checkboxes in the "Faults" register of the target system
> Faults/Warnings/Events mask.
Controlling
Indication
Meaning/Possible cause/Acknowledgement/Error processing
Execution ON command The motor feeder could not be turned on after an ON command.
Possible causes:
Main circuit is interrupted (fuse, circuit breaker)
Motor contactor or contactor control is defective
Parameter execution time is too short.
Acknowledge with "Reset" or OFF command/counter command.
Execution stop command The motor feeder could not be turned off after a Stop command.
Possible causes:
The contactor contact is welded
Parameter execution time is too short
The "Open" end position has not been reached during the
parameterized runtime (only in the case of the "Slider" and
"Valve" control functions.
Following fault rectification, acknowledge with "Reset".
Feedback (F) ON The motor feeder could not be turned on after an ON command.
Possible causes:
Main circuit is interrupted (fuse, circuit breaker)
Motor contactor or contactor control is defective, "Execution
time" parameter is too short.
Only in the case of the "Slider/Solenoid valve" control
function. The end position "CLOSE" has not been reached
during the parameterized runtime.
Following fault rectification, acknowledge with "Reset" or OFF
command.
Feedback (F) OFF The current flow in the motor feeder was interrupted without the
motor feeder being turned off.
Possible causes:
Main circuit is interrupted (fuse, circuit breaker, main switch)
Motor contactor or contactor control is defective.
Acknowledge with "Reset" respectively OFF command.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals