Online Settings and Displays
17.11 Warnings
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
159
Meaning/Possible cause/Acknowledgement/Error processing
Thermistor short circuit A short circuit has occurred in the thermistor sensor cable.
Check the thermistor sensor cable and the thermistor.
After fault repair acknowledge with "Reset".
Further information: Thermistor.
Thermistor open circuit A wire break has occurred in the thermistor sensor cable.
Check the thermistor sensor cable and the thermistor.
After fault repair acknowledge with "Reset".
Further information: Thermistor.
Temperature Module 1/2 sensor
fault
Either a short circuit or a wire break has occurred in the
temperature sensor circuit.
Check the temperature sensor and the sensor cable.
Acknowledge with "Reset".
Temperature Module 1/2 out of
range
The temperature sensor is yielding values which are not
permitted.
Check the temperature sensor.
Acknowledge with "Reset".
Parameterization Parameterization faulty:
• Parameterize again.
• Switch the control voltage off and on.
Test shutdown The motor feeder was checked and switched off by a test
switch-off.
Acknowledge with "Reset".
Operational Protection Off (OPO) The "Operational Protection Off" signal (OPO) is pending.
A switched-on motor feeder was switched off.
Switching on is not possible as long as the OPO signal is
pending.
Acknowledge with "Reset".
17.11 Warnings
Warnings
Different warnings are indicated via lamp symbols in the "Warnings" register of the target
system > Faults/Warnings/Events mask.