Online Settings and Displays
17.10 Faults
SIMOCODE PRO V PN FDI
158 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Miscellaneous - General
Meaning/Possible cause/Acknowledgement/Error processing
External Fault 1 to 6 A signal is pending at the input (socket) of the standard
function.
External fault 1, 2, 3, 4,5 or 6.
Check the motor feeder.
Acknowledgement depends on parameterization.
Further information: External Fault (1 to 6).
Bus The PROFINET communication has been or is being
interrupted.
Check the PROFINET connection (plugs, cables, etc).
Acknowledge with "Reset", if Auto-Reset is not activated.
Further information:Watchdog (PLC/DCS monitoring)
PLC/DCS The PLC which controls the feeder was or is in the STOP state.
Check the operating status of the PLC.
Acknowledge with "Reset", if Auto-Reset is not activated.
Further information: Watchdog (Bus Monitoring, PLC/DCS
Hardware fault Basic Unit The hardware of the SIMOCODE pro basic device is defective.
Module fault At least one SIMOCODE pro module is not ready for use.
Possible causes:
• Connecting cable is defective or has not been plugged in
correctly.
• Module is defective. Replace the module.
Acknowledge with "Reset".
Temporary components Fault - Temporary components (memory module, addressing
plug, PC cable).
Replace the defective component.
Acknowledge with "Reset".
Configuration fault The configured device configuration does not match the current
configuration.
Approach:Check if all configured components are present.
Check the actual configuration using "Configuration".
Acknowledge with "Reset".
Further information: Actual configuration.
analog module 1/2 open circuit A wire break has occurred in the analog value measuring
circuit.
Check the measuring transducer and the measuring circuit.
Acknowledge with "Reset".
Further information: Analog Module.