Monitoring Functions
9.8 Temperature
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
65
Response at Overshoot
Here you can set the response for when the Number of Starts within the Time Range for
Starts has been overshot.
Interlocking Time (CiR)
If a new start command is issued within the time range for starts after the last permissible
start, this new start command will no longer be executed if the setting "Response at
Overshoot Tripping" has been set. "Trip - No. of Starts>" will be displayed and the set
Interlocking Time activated.
9.8 Temperature
Temperature T> (Upper limit)
Temperature monitoring of, for example, motor windings, motor bearings, coolant and
gearbox temperature, can be carried out via up to 3 analog temperature sensors such as
NTC, KTY 83/84, Pt100, Pt1000. SIMOCODE pro supports 2-phase monitoring for
overtemperature: Separate levels can be set for the warning temperature and the switch-off
temperature.
Temperature Monitoring is based upon the highest temperature in all sensor measuring
circuits of the Temperature Module.
Settings
-273°C to 65262°C (Preset: -273°C)
Response at Trip level T>
en the temperature is overshot (see the
following table "response")
No parameters. Optional marking for designation of the
signal, e.g. "Temperature>". Range: up to 10 characters
-273°C to 65262°C (Preset: -273°C)