Motor Protection
7.3 Stalled Rotor
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
29
7.3 Stalled Rotor
Stalled Rotor
After the motor current exceeds an adjustable stall limit (current limit), a definable and
delayable response can be parameterized in SIMOCODE pro. For example, the motor can
be set to be tripped quickly independently of the overload protection. The stall protection is
only active after the parameterized class interval has elapsed, e.g. for class 10 after 10
seconds. The stall protection prevents the motor from unnecessary high thermal and
mechanical load as well as premature deterioration.
Level (CiR)
After exceeding the stall limit, SIMOCODE pro reacts according to the specified response.
Level:
0 up to 1020 % of I
s
Response
Here you can determine the response to be executed when the blocking limit is exceeded:
Response
Overload
Disabled
X
Signaling
X
Warning
X
Tripping
X
Delay (CiR)
The "Delay" parameter is used to specify the time interval. The stall level must be constantly
exceeded before SIMOCODE pro executes the desired response. Otherwise there is no
reaction.
Delay:
0 to 25.5 s
Preset:
0.5 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals