Monitoring Functions
9.2 Current Limits
SIMOCODE PRO V PN FDI
50 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
9.2.2 I> (upper limit)
Trip level (CiR), warning level (CiR)
When monitoring Current Limits I> (upper limit), 2 different response levels, I> (upper limit)
trip level and I> (upper limit) warning level, can be parameterized and monitored. If the
current of one or more phases exceeds the response level, Current Limits monitoring is
activated.
Trip level
0 to 1020 % of I
s
in 4 % increments
Warning level
0
to 1020 % of I
s
in 4 % increments
Response, Delay (CiR) at trip level
Here you can set:
how SIMOCODE pro should respond when the trip level is overshot
the delay time.
Response
Trip level
Disabled
X
Signaling
X
Warning
-
Tripping
X
Delay
0 to 25.5 s
Preset
0.5 s
Response, Delay (CiR) at warning level
Here you can set:
how SIMOCODE pro should respond when the warning level is overshot
the delay time.
Response
Warning level
Disabled
X
Signaling
X
Warning
X
Tripping
-
Delay
0 to 25.5 s
Preset
0.5 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals