Standard Functions
12.3 External Fault
SIMOCODE PRO V PN FDI
92 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Settings Type, Activity, Marking
Type
Specification the input logic:
NO contact (1-active)
NC contact (0-active)
Activity
To specify in which motor operating state the External Fault to be
evaluated:
Always
:
Always evaluate, regardless of whether the motor is running at a
standstill.
Only when the motor is ON:
Evaluation only when the motor is switched ON
Marking
No parameters. Optional marking to designate the signal, e.g.
"rotational speed >", e.g. using Device Integration Manager. Range: up
to a maximum of 10 characters.
12.3.2.2 External Faults 1-6 Inputs
External Faults 1-6 Inputs
Settings:
Input
Control of the External Fault function block using the monitored signal
(any sockets, e.g. device inputs, control bits from PROFINET, etc.)
Reset
Acknowledgment the "External Fault" using any signal (any socket ,
e.g. device inputs, control bits from PROFINET, etc.).
Response
Specification of the response to an External Fault when activated via
the Input (see the following table)
Response:
Response
External fault
Fault/Tripping
X
Warning
X
Signaling
X
Disabled
-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals