SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
141
Online Settings and Displays
17.1 Error Buffer - Error Protocol
17.1.1 Error Buffer - Error Protocol
Error Buffer - Error Protocol
See Error Buffer - Error Protocol - Events (Page 141)
See Error Buffer - Error Protocol - Events DM-F (Page 142)
17.1.2 Error Buffer - Error Protocol - Events
Error Buffer - Error Protocol - Events
The timestamping in the fault memory is based on the operating hours (resolution: 1 s) of
SIMOCODE pro.
The "Error/Fault" and "Mains on" events are recorded. Each of these events are annotated
with a timestamp.
● Error/Fault:
The last 21 faults are stored in a ring buffer. The fault that occurs (rising edge) is always
recorded. A fault that is disappearing (falling edge) is not recorded.
● Mains on:
If the most recent entry was "Mains on", this is not recorded multiple times. Instead, the
fault number is used as a mains-on counter. This means that the fault memory cannot be
deleted by frequent ON/OFF operations.
Entry 1 is the most recent entry and entry 21 the oldest.