Monitoring Functions
9.6 0-20 mA - 4-20 mA
SIMOCODE PRO V PN FDI
60 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
9.6 0-20 mA - 4-20 mA
9.6.1 0-20 mA - 4-20 mA
Monitoring 0/4-20 mA
SIMOCODE pro supports two-phase monitoring of the analog signals of a transducer
standard 0/4-20 mA output signal. The analog signals are fed to the "0/4-20mA" function
block via the Analog Module:
Trip Level (CiR), Warning Level (CiR)
With 0/4-20 mA Monitoring, you can parameterize two different response levels (Trip
Level/Warning Level) for the upper and lower limit:
0/4-20> (upper limit)
0/4-20< (lower limit)
- 23,6 mA
0/4-20> (upper limit)
0/4-20< (lower limit)
Activity Trip Level, Warning Level
Here you can specify in which motor operating states the Trip Level/Warning Level is to take
effect:
Trip Level/Warning Level always takes effect,
regardless of whether
the motor is running or
Always, except in the case of TPF (on+)
Trip Level/Warning Level always takes effect,
regardless of whether the motor is running or
stationary with the exception of "TPF", i.e.
motor feeder is in test position
When the motor is on, except in the case
of TPF (run)
Trip Level/Warning Level only takes effect if
the motor is on and not in the test position
When the motor is on, except in the case
of TPF, with start hiding (run+)
The Trip Level/Warning Level only takes
e
ffect if the motor is running and the start-up
procedure is finished, and there is no test
position feedback (TPF)