Motor Control
8
8.1 Motor Control
Motor Control
You can select and enable control stations according to requirements here.
8.2 Control Station
8.2.1 Control Station
Control Station
Control stations are places from which control commands can be given to the motor. The
Control Stations function block is used for the management, switching and prioritization of
these different control stations.
With this, SIMOCODE pro allows the parallel administration of up to four different control
stations. Dependent on the specified control function, up to 5 different control commands can
be transmitted from every control station to SIMOCODE pro.
Local Control (in the direct vicinity of the motor): Control commands are issued via push
button.
PLC/DCS: Switching commands are issued by the automation system (remote).
PC: Control commands are issued via an operator control station or via PROFINET with
the Device Integration Manager.
Operator Panel: Control commands are issued via the buttons of the Operator Panel in
the switchgear cabinet door.
Control commands can be e.g.:
Motor ON (ON>), Motor OFF (OFF) for a direct starter
Motor LEFT (ON<), Motor OFF (OFF), Motor RIGHT (ON>) for a reversing starter
Motor SLOW (ON>), Motor FAST (ON>>),Motor OFF (OFF) for a Dahlander circuit.
The plugs of the Control Stations function block must be connected to arbitrary sockets (e.g.
binary inputs on the Basic Unit, control bits from PROFINET) for the control commands to
take effect.
Up to 5 different control commands can be sent from each control station. There are up to 5
plugs (plug ON<<, ON<, OFF, ON>, ON>>) available on the function block per control
station. The number of active plugs depends on the chosen control function. With a direct
starter, for example, only the plugs "ON>" and "OFF" are active.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals