Online Settings and Displays
17.11 Warnings
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
163
Indication
Meaning/Possible cause/Acknowledgement/Error processing
Warning level T> Temperature module 1/2 - warning level overshot.
Check the temperature measuring station.
Further information: Analog Temperature Monitoring (Page 65).
DM-F - Test requirement The DM-F Local / DM-F PROFIsafe enabling circuits have not
been opened and closed again within the configured time period.
The function of the enabling circuit relay contacts can only be
tested when they are switched.
Please adopt the measures intended for this case.
Miscellaneous - General
Indication
Meaning/Possible cause/Acknowledgement/Error processing
External Fault 1 to 6 A signal is pending at the input (socket) of the standard
function.
External fault 1, 2, 3, 4,5 or 6.
Check the motor feeder.
Further information: External Fault (1 to 6).
Analog Module 1/2 open circuit A wire break has occurred in the analog value measuring
circuit.
Check the measuring transducer and the measuring circuit.
Acknowledge with "Reset".
Further information: Analog Module.
Thermistor short circuit A short circuit has occurred in the thermistor sensor cable.
Check the thermistor sensor cable and the thermistor.
After fault repair acknowledge with "Reset".
Further information: Thermistor (Page 30).
Thermistor open circuit A wire break has occurred in the thermistor sensor cable.
Check the thermistor sensor cable and the thermistor.
After fault repair acknowledge with "Reset".
Further information: Thermistor (Page 30).
Temperature Module 1/2 sensor
fault
Either a short circuit or a wire break has occurred in the
temperature sensor circuit.
Check the temperature sensor and the sensor cable.
Acknowledge with "Reset".
Temperature Module 1/2 out of
range
The temperature sensor is yielding values which are not
permitted.
Check the temperature sensor.
Acknowledge with "Reset".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals