Page #38 background imageLoading...
Page #38 background image
Motor Control
8.3 Control Function
SIMOCODE PRO V PN FDI
38 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Parameter
Description
DM
-F LOCAL/DM-F PROFIsafe -
separate function from the control
function
Deactivated
:
A safety-oriented tripping via the DM-F module also
affects the SIMOCODE pro control function, so that
the contactor control is always tripped, too.
This setting is selected for applications where a
safety-oriented tripping directly affects the motor
controlled by SIMOCODE pro.
Activated:
A safety-oriented tripping via the DM-F module does
not affect the SIMOCODE pro control function, so
that the contactor control is not tripped.
This setting is selected for applications where a
safety-oriented tripping does not affect the motor
controlled by SIMOCODE pro.
Type of consumer load
You can choose between:
Motor
and
Resistive load (e.g. heating)
Because generally no
overcurrent flows in a resistive
load during switching, the "Start Active" status is not
signaled. In this case, the start
-up override does not
occur for the "signaling", "warning" and "tripping"
functions.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals