Monitoring Functions
9.3 Voltage U< (lower limit)
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
53
Response, Delay (CiR) at trip level
Here you can set:
● how SIMOCODE pro should respond when the trip level is undershot
● the delay time.
Response, Delay (CiR) at warning level
Here you can set:
● how SIMOCODE pro should respond when the trip level is undershot
● the delay time.
Hysteresis for voltage, cos-phi, power
The hysteresis for voltage, cos phi and power can be set here:
0 to 15 % of the threshold value in 1 % increments (5 %)