Monitoring Functions
9.5 Active Power
SIMOCODE PRO V PN FDI
56 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Warning Level
P> (upper limit)
0
to 4294967.295 kW
P< (lower limit)
Trip level and warning level activity
The trip level/warning level is only effective when the motor is running, the start-up
procedure has been completed and there is no Test Position Feedback (TPF) (run+).
Response, Delay (CiR) at trip level:
Here you can set:
how SIMOCODE pro should respond if the set Trip Level is either undershot or overshot
the delay time.
Response
Trip level
Disabled
X
Signaling
X
Warning
-
Tripping
X
Delay
0 to 25.5 s
Preset
0.5 s
Response, Delay (CiR) at warning level
Here you can set:
how SIMOCODE pro should respond if the set warning level is overshot
the delay time.
Response
Warning level
Disabled
X
Signaling
X
Warning
_
Tripping
-
Delay
0 to 25.5 s
Preset
0.5 s