Outputs
11.5 Analog Module Outputs
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
81
2. Output of the Effective Motor Current - only part of the motor current range (overload
range).
The Motor Current of a motor ranges from 0 to 8 A.
The Rated Current I
N
of the motor at nominal load is 2 A.
The parameterized Set Current I
s
in Device Integration Manager corresponds to the
Rated Current I
N
(2 A). However, only the overload range (2 A - 8 A) is to be displayed on
a pointer instrument via the Analog Module Output.
In SIMOCODE pro, representation of the effective phase currents or the maximum
current (current IL_1, IL_2, IL_3, max. current I_
max
) corresponds to the selected range as
a percentage of the parameterized Set Current I
s
:
0 A motor current corresponds to 0 % of I
s
8 A motor current corresponds to 400 % of I
s
The smallest unit for the effective motor current in SIMOCODE pro is 1 %.
As a result,
the "start value of value range (CiR)" to be selected is: 100
the "end value of value range (CiR)" to be selected is: 400.
When the parameterized "output signal" = 0 - 20 mA:
100 % Motor Current corresponds to: 0 mA at the Analog Module Output
400 % Motor Current corresponds to: 20 mA at the Analog Module Output.
When the parameterized "Output Signal" = 4 - 20 mA:
100 % Motor Current corresponds to: 4 mA at the Analog Module Output
400 % Motor Current corresponds to: 20 mA at the Analog Module Output.
3. Output of any analog value from the automation system, cyclically via PROFINET.
1 word (2 byte) can be cyclically transmitted from the automation system to SIMOCODE
pro via PROFINET. Any value can be output as a 0/4 to 20 mA signal by directly
connecting this cyclic control word from PROFINET to the Analog Module Output. If the
transmitted value is in S7 Format (0 to 27648) it must be taken into consideration when
parameterizing:
As a result,
the "start value of value range (CiR)" to be selected is: 0
the "end value of value range (CiR)" to be selected is: 27648.
When the parameterized "output signal" = 0 - 20 mA:
0: 0 mA at the analog module output
27648: 20 mA at the analog module output.
When the parameterized "output signal" = 4 - 20 mA:
0: 4 mA at the Analog Module Output
27648: 20 mA at the Analog Module Output.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals