Di󹪜erent operating modes
Local / Remote : In Local mode, the block control is switched o󹪜. SIMOCODE-DP is controlled
through the local control station or the operator panel.
In Remote mode, SIMOCODE-DP is controlled through the PLC / CPU control station of the
block.
Automatic : In Automatic mode, SIMOCODE-DP is controlled by a program through linked
block signals.
Manual : In Manual mode, SIMOCODE-DP is controlled by an operator through the OS, or
linked block inputs.
The SIMOCODE-DP is controlled and monitored using data from the process image. Moreover,
data records containing statistical and diagnostic information can be read or written by
means of acyclic DPV1 services (if integrated through GSD sie?8069.gs?).
4.1.4 Principle of Operation
In program 󹪝le Blocks+Templates\Templates, the SIMOCODE DP PCS 7 Library Migration (Legacy)
provides templates for each control function.
The control function dependent parameters, and the messages to appear on the faceplates,
are preset with suitable values in the templates. These templates can be used as models
for making customized automation solutions. To do this, copy the SIMO_CHN block for the
desired control function from the corresponding CFC plan, and insert it in your own CFC plan.
The control function (OVL, DIR, REV, STAR, DAHL, POL, VALVE, POS, SOFT) is con󹪝gured at
the block through input "SIMO_FCT". Depending on the setting selected, the corresponding
functions are enabled in the block and the various displays in the OS components.
4.1.5 Module Failure
If an invalid process value is indicated by MODE, outputs QCSF and CUR_QC are set.
4.1.6 Simulation
Simulation mode is switched on through the SIM_ON input and has higher priority than all other
modes.
If SIM_ON=TRUE, the block processes the simulation values (SIM_I01: binary data;
SIM_I23: motor current) instead of the SIMOCODE-DP process values (INBT2_01,
INBT2_23). QSIM and CUR_QC are output accordingly. The process outputs to SIMOCODE-
DP (OBT2_01, OBT2_23) are output as "0" when simulation is switched on.
Output QBAD is set depending on QCSF and QSIM (QBAD= QCSF AND NOT QSIM). In normal
operation (SIM_ON=FALSE), the value corresponds to output QCSF and indicates an invalid
process value. A simulation value can thus be treated as a valid process value for testing
purposes, in the event of an error.
SIMO_CHN Function
4.1Description
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2
40 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE DP and is the answer not in the manual?

Siemens SIMOCODE DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE DP
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals