4.1.11 Monitoring of Control Commands
The monitoring logic checks whether the output commands match the read check-back
signals. It sets a monitoring error (QMON_ERR=1) if a check-back signal changes
unexpectedly (e.g. due to a command enabled directly at the SIMOCODE-DP Local Control
Station in REMOTE mode) or if an output command has not become active after
the TIME_MON period has elapsed.
The monitoring error is reset at the OS through the RESET input or through linkable
input L_RESET. If L_RESET=1 is set continuously, output QMON_ERR remains set for one
program cycle if the above conditions are present.
Monitoring is active if a QMONITOR=TRUE output is set. This is the case if MONITOR=TRUE,
TIME_MON>0 and SAMPLE_T>0.
Monitoring is not active while lock time QLTA is running, or if a higher-level error (QCSF) or
general fault in SIMOCODE-DP (QG_FLT) is present.
4.1.12 Motor Current Monitoring
This block monitors the read motor current. Any value above or below the limit value is indicated
by corresponding outputs, and indicated where appropriate.
The limit values are con󹪝gured at the OS through inputs CUR_AH, CUR_WH, CUR_WL, and
CUR_AL. A hysteresis value HYS can also be set. The indications are provided through
outputs QCUR_AH, QCUR_WH, QCUR_WL, and QCUR_AL. Output QCUR is used to indicate
whether a current is 󹪞owing.
Motor monitoring is only active when the current goes above minimum value CUR_MIN
(default value of CUR_MIN=20%). Also, motor monitoring is inhibited after the motor
is switched on, i.e. when the signal edge of QCUR (0->1) changes for the duration of
TIME_CLASS (default value 10s). The time set with the TIME_CLASS parameter should
match the time class con󹪝gured in the SIMOCODE-DP. Special case: the duration for STAR is
2.1 x TIME_CLASS.
The display range and limits for the motor current are set through inputs MO_PVHR and
MO_PVLR.
4.1.13 Statistic and Diagnostic Functions
If con󹪝gured accordingly (see Con󹪝guration (Page28)), SIMOCODE-DP provides data records
containing statistic and diagnostic information.
When SIMO_DPV1 is enabled, the system functions RD_REC and WR_REC are used to access
the data records 130, 131, and 133. Input SIMO_DPV1 and address LADDR are con󹪝gured
through the CFC Generate Module Drivers function, using the hardware con󹪝guration.
For controls from the OS, enable signal QENSDCS is also required. In this case, output
QENSDCS is set depending on inputs SIMO_DPV1 and EN_SD_CS.
SIMO_CHN Function
4.1Description
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2
Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003 43

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE DP and is the answer not in the manual?

Siemens SIMOCODE DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE DP
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals