C
Modbus
™
RTU Communications Protocol
SIMPRO-100
174 PRIM-2400C
01CB yyyy 0 65535 1
01CC Last Reset Time hh, mm 0, 0 23, 59 1, 1
01CD ssss 0 5999 1 • 0.01
01CE Reserved
01CF Reserved
PEAK DEMAND METERING
01D0 Ia Peak Demand 0 65535 1
01D1 Ib Peak Demand 0 65535 1
01D2 Ic Peak Demand 0 65535 1
01D3 In Peak Demand 0 65535 1
01D4 Ig Peak Demand 0 65535 1
01D5 3I2 Peak Demand 0 65535 1
01D6 kW3P Peak Demand 0 if no voltage option 0 65535 1
01D7 kVAR3P Peak Demand In 0 if no voltage option 0 65535 1
01D8 kVAR3P Peak Demand Out 0 if no voltage option 0 65535 1
01D9 kVA3P Peak Demand 0 if no voltage option 0 65535 1
01DA Last Reset Date mm, dd 1, 1 12, 31 1, 1
01DB yyyy 0 65535 1
01DC Last Reset Time hh, mm 0, 0 23, 59 1, 1
01DD ssss 0 5999 1 • 0.01
01DE Reserved
01DF Reserved
CURRENT MAX/MIN METERING
01E0 Ia Max Current (FFFFh if reset) 0 65535 1
01E1 Ia Max Current Date mm, dd (FFFFh if reset) 1, 1 12, 31 1, 1
01E2 yyyy (FFFFh if reset) 0 65535 1
01E3 Ia Max Current Time hh, mm (FFFFh if reset) 0, 0 23, 59 1, 1
01E4 ssss (FFFFh if reset) 0 5999 1 • 0.01
01E5 Ia Min Current (FFFFh if reset) 0 65535 1
01E6 Ia Min Current Date mm, dd (FFFFh if reset) 1, 1 12, 31 1, 1
01E7 yyyy (FFFFh if reset) 0 65535 1
01E8 Ia Min Current Time hh, mm (FFFFh if reset) 0, 0 23, 59 1, 1
01E9 ssss (FFFFh if reset) 0 5999 1 • 0.01
01EA Ib Max Current (FFFFh if reset) 0 65535 1
01EB Ib Max Current Date mm, dd (FFFFh if reset) 1, 1 12, 31 1, 1
01EC yyyy (FFFFh if reset) 0 65535 1
01ED Ib Max Current Time hh, mm (FFFFh if reset) 0, 0 23, 59 1, 1
01EE ssss (FFFFh if reset) 0 5999 1 • 0.01
01EF Ib Min Current (FFFFh if reset) 0 65535 1
Address
(hex)
Field Sample Low High Step Type