A1.STPOS - Start position
Adjustment range: 0.0 ... 100.0
Purpose: Use this sub-parameter to define the start position of the partial
stroke test in percent. Set the start position in a range from "0.0" to
"100.0". The triggering of alarms (limits) is relative to the MPOS
scale.
The actuator moves during the partial stroke test from the start po‐
sition to the target position. The target position is determined from
the interaction between start position (A1.STPOS), stroke height
(A3.STRKH) and stroke direction (A4.STRKD).
Factory setting: 100.0
A2.STTOL - Start tolerance
Adjustment range: 0.1 ... 10.0
Purpose: Use this sub-parameter to assign the start tolerance of the partial
stroke test in percent. Set the start tolerance relative to the start
position in a range from "0.1" to "10.0".
Example: You have set "50.0" as start position and "2.0" as start tolerance. In
this case, a Partial Stroke Test is initiated during operation only
between a position of 48% and 52%.
Factory setting: 2.0
A3.STRKH - Stroke height
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to assign the stroke height of the partial
stroke test in percent. Set the stroke height in a range from "0.1" to
"100.0".
Factory setting: 10.0
A4.STRKD - Stroke direction
Possible settings: uP
do
uP do
Purpose: Use this sub-parameter to assign the stroke direction of the partial
stroke test.
uP: Actuator only moves upward
The actuator moves from its start position to the upper target
position.
After reaching the upper target position, the actuator moves
back to the start position.
Parameter assignment
8.3 Description of parameters
SIPART PS2 with PROFIBUS PA
164 Operating Instructions, 05/2019, A5E00127926-AC

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h

Related product manuals